基于IEEE Std C37.2™-2008标准和《电气工程名词》进行翻译校准

东方欲晓,莫道君行早      ——    李德胜

3.1.31 Device number 31—separate excitation device

A device that connects a circuit, such as the shunt field of a synchronous converter, to a source of separate excitation during the starting sequence.

31-他励元件

一种在起动程序期间将类似同步换流器的分激磁场之类的电路街道他激磁场的电源上的装置。

3.1.32 Device number 32—directional power relay

A device that operates on a predetermined value of power flow in a given direction, such as reverse power flow resulting from the motoring of a generator upon loss of its prime mover.

32-功率方向继电器

是一种按指定方向流动的功率达到要求值时,才动作的装置;或在功率整流器的正极或负极电路中,由逆弧引起的反向功率下动作的装置。

3.1.33 Device number 33—position switch

A device that makes or breaks contact when the main device or piece of apparatus that has no device function number reaches a given position.

33-位置开关

此代号的装置的主要元件或设备零部件的工作位置达到某一指定的位置时接通或断开接触。

3.1.34 Device number 34—master sequence device

A device such as a motor-operated multi-contact switch (or the equivalent), or a programmable device, that establishes or determines the operating sequence of the major devices in equipment during starting and stopping, or during sequential switching operations.

34-主程序元件

一种装置,如电动机多接点开关之类,或可编程装置,它在起动或停机期间,或在其他程序切换动作期间,建立或确定设备中主要装置的操作顺序。

3.1.35 Device number 35—brush-operating or slip-ring short-circuiting device

A device for raising, lowering, or shifting the brushes of a machine; short-circuiting its slip rings; or engaging or disengaging the contacts of a mechanical rectifier.

35-加速或减速元件

用以抬起、放低或移动电机的电枢,或短接其滑环、或用以接通或切断机械式整流器的接点。

3.1.36 Device number 36—polarity or polarizing voltage device

A device that operates, or permits the operation of, another device on a predetermined polarity only, or that verifies the presence of a polarizing voltage in equipment.

36-极性或极化电压元件

一种仅在规定极性下动作,或允许另一设备动作,或验证设备中是否存在极化电压的装置。

3.1.37 Device number 37—undercurrent or underpower relay

A device that functions when the current or power flow decreases below a predetermined value.

37-欠电流或低功率继电器

在电流或功率降低到定值下动作

3.1.38 Device number 38—bearing protective device

A device that activates upon excessive bearing temperature or on other abnormal mechanical conditions associated with bearings, such as undue wear, which may eventually result in excessive bearing temperature or failure.

38-轴承保护元件

在轴承温度过高或与轴承相关的其他异常机械状况下动作的一种设备。(如过度磨损,可能最终导致轴承温度过高或故障。)

3.1.39 Device number 39—mechanical condition monitor

A device that activates upon the occurrence of an abnormal mechanical condition (except conditions associated with bearings as covered under device function 38), such as excessive vibration,eccentricity, expansion, shock, tilting, or seal failure.

39-机械状况监控器

一种发生异常机械状况时动作的设备(不包括与轴承有关的38号装置),如过度振动、偏心、膨胀、冲击、倾斜或密封失效。

3.1.40 Device number 40—field (over / under excitation) relay

A device that activates upon a given or abnormally high or low value or failure of machine field current, or on an excessive value of the reactive component of armature current in an ac machine indicating abnormally high or low field excitation

.40-励磁(/欠励磁)继电器

在电机的磁场电流达到一定值,或降到不正常的低值,或没有磁场的电流时动作,或在一个指示不正常的低磁场激励的交流电机中,电枢无功电流异常高时动作。

3.1.41 Device number 41—field circuit breaker

A device that functions to apply or remove the field excitation of a machine.

41-励磁断路器

是一种用来为电机加励磁或去励磁的装置。

3.1.42 Device number 42—running circuit breaker

A device whose function is to connect a machine to its source of running or operating voltage. This function may also be used for a device, such as a contactor, that is used in series with a circuit breaker or other fault-protecting means, primarily for frequent opening and closing of the circuit.

42-工作回路断路器

一种装置,其作用是将电机接到它的运行或工作电压源上。这一功能也可像接触器一类的装置,用于与断路器或其他故障保护装置串联使用,主要用于电路的频繁开合的断路器。

3.1.43 Device number 43—manual transfer or selector device

A manually operated device that transfers control or potential circuits in order to modify the plan of operation of the associated equipment or of some of the associated devices.

43-手动转换或选择元件

用来转换控制电路,以便修改开关设备或某些装置的运行逻辑。

3.1.44 Device number 44—unit sequence starting relay

A device that functions to start the next available unit in multiple-unit equipment upon the failure or nonavailability of the normally preceding unit.

44-单元(机组)顺序起动继电器

用于多单元(机组)设备中,由于前一单元(机组)发生故障或不能正常运行时,起动下一单元(机组)的装置。

3.1.45 Device number 45—abnormal atmospheric condition monitor

A device that functions upon the occurrence of an abnormal atmospheric condition, such as damaging fumes, explosive mixtures, smoke, or fire.

45-大气状况监视器

一种能在异常的大气条件下(如有害的烟雾、爆炸性混合物、烟雾或火灾)起作用的装置。

3.1.46 Device number 46—reverse-phase or phase-balance current relay

A device in a polyphase circuit that operates when the polyphase currents are of reverse-phase sequence, or when the polyphase currents are unbalanced, or when the negative phase-sequence current exceeds a preset value.

46-反相或相平衡电流继电器

是一种当多相电流为负相序,或当多相电流不平衡,或包含的负序分量超过定值时动作的继电器。

3.1.47 Device number 47—phase-sequence or phase-balance voltage relay

A device in a polyphase circuit that functions upon a predetermined value of polyphase voltage in the desired phase sequence when the polyphase voltages are unbalanced, or when the negative phase-sequence voltage exceeds a preset value.

47-相序电压电器

一种多相电路中的装置,当多相电压不平衡或负相序电压超过预定值时,它在所要求发相序下对锁定的多相电压起作用。

3.1.48 Device number 48—incomplete sequence relay

A device that returns the equipment to the normal or off position and locks it out if the normal starting,operating, or stopping sequence is not properly completed within a predetermined time.

48-非全相序继电器

是一种在预定的时间内,不能正确的完成正常的起动、运转、或停机程序时,通常使设备回到正常或断开位置,并将其闭锁的继电器。

3.1.49 Device number 49—machine or transformer thermal relay

A device that functions when the temperature of a machine armature winding or other load-carrying winding or element of a machine or power transformer exceeds a predetermined value.

49-电机或变压器过热继电器

当电机电枢绕组或其他负载绕组或电机元件或电力变压器的温度超过预定值时起作用的一种装置。

3.1.50 Device number 50—instantaneous overcurrent relay

A device that operates with no intentional time delay when the current exceeds a preset value. The suffix TD should be used (e.g., 50TD) to describe a definite time overcurrent function. Use 50BF for a currentmonitored breaker failure function.

50-瞬时过电流继电器

一种当电流超过预设值时不经过延时而瞬时动作的装置。后缀TD应该用来描述一个明确的时间过流函数(例如,50TD)。 使用50BF作为电流监测断路器故障功能。

IEEE 继电保护代码中英文对照(31-50)相关推荐

  1. 《Empyrion-Galactic Survival》所有物品方块科技等代码名称中英文对照(修改数据用)

    <Empyrion-Galactic Survival>所有物品方块科技等代码名称中英文对照(修改数据用) 游戏名:Empyrion-Galactic Survival(帝国霸业银河生存) ...

  2. AlexNet论文翻译(中英文对照版)-ImageNet Classification with Deep Convolutional Neural Networks

    图像分类经典论文翻译汇总:[翻译汇总] 翻译pdf文件下载:[下载地址] 此版为中英文对照版,纯中文版请稳步:[AlexNet纯中文版] ImageNet Classification with De ...

  3. 图像分类经典卷积神经网络—ResNet论文翻译(中英文对照版)—Deep Residual Learning for Image Recognition(深度残差学习的图像识别)

    图像分类经典论文翻译汇总:[翻译汇总] 翻译pdf文件下载:[下载地址] 此版为中英文对照版,纯中文版请稳步:[ResNet纯中文版] Deep Residual Learning for Image ...

  4. 宇宙最强,meltdown论文中英文对照版(三)

    本文由郭健郭大侠翻译,将分为三次连载完成,这是第三部分.郭大侠是蜗窝科技(http://www.wowotech.net/)的创始人,倡导"慢下来,享受技术"的健康理念,侠之大者, ...

  5. 目标检测经典论文——R-FCN论文翻译(中英文对照版):Object Detection via Region-based Fully Convolutional Networks

    目标检测经典论文翻译汇总:[翻译汇总] 翻译pdf文件下载:[下载地址] 此版为纯中文版,中英文对照版请稳步:[R-FCN纯中文版] R-FCN: Object Detection via Regio ...

  6. 深度学习论文阅读目标检测篇(四)中英文对照版:YOLOv1《 You Only Look Once: Unified, Real-Time Object Detection》

    深度学习论文阅读目标检测篇(四)中英文对照版:YOLOv1< You Only Look Once: Unified, Real-Time Object Detection> Abstra ...

  7. D2x神符之语中英文对照图文豪华版

    D2X神符之语中英文对照图文豪华版 *:战网专有  ※:天梯模式专有  ♠:1.11新增非专有 D2x1.11神符之语  D2x1.10神符之语  D2x1.09神符之语 常用神符之语索引 防具类 谜 ...

  8. RFC2326 - Real Time Streaming Protocol (RTSP) 完整中英文对照版

    RFC2326 - Real Time Streaming Protocol (RTSP) 完整中英文对照版 E-mail:bryanj@163.com 译者: Bryan.Wong(王晶,宁夏固原) ...

  9. 图像分类经典卷积神经网络—GoogLeNet论文翻译(中英文对照版)—Going Deeper with Convolutions(走向更深的卷积神经网络)

    图像分类经典论文翻译汇总:[翻译汇总] 翻译pdf文件下载:[下载地址] 此版为中英文对照版,纯中文版请稳步:[GoogLeNet纯中文版] Going Deeper with Convolution ...

最新文章

  1. 这次我让你彻底弄懂 RESTful
  2. 6个步骤卸载wine
  3. nmealib解析-----(1)
  4. 那些年踩过的eleUl上传图片的坑?
  5. [转载] Numpy数组对象ndarray
  6. 普元云计算-你适合微服务么:实施微服务的4个先决条件和重点工作
  7. 班级信息管理c语言代码,C语言班级信息管理系统(有详细代码).doc
  8. 将钉钉应用内浮窗_手机钉钉怎么设置悬浮窗 几步轻松开启
  9. Week 10 homework
  10. win10u盘一直正在计算机,Windows10未插入U盘却一直显示的解决方法
  11. mysql创建临时表
  12. vscode 文件夹中查找_VSCode 多文件搜索和替换
  13. Smoke Screener or Straight Shooter: Detecting Elite Sybil Attacks in User-Review Social Networks阅读笔记
  14. 工作能力强的人,都有哪些特点?
  15. 20亿美金独角兽Notion,和它在中国的“抄袭”者们
  16. 【Java并发编程(一)】并发设计原理
  17. 【jiasuba】分享:键盘失灵烦恼多 教你轻松禁用原键盘
  18. spring boot 和cloud 版本升级
  19. LOJ #573. 「LibreOJ NOI Round #2」单枪匹马 线段树
  20. Java的基础语法——数据类型

热门文章

  1. Java 音乐播放器开发学习之——音频文件的播放
  2. jieba词频统计、关键词提取、词云图制作
  3. 为什么吃鸡进不去显示服务器,为什么吃鸡进不去游戏显示服务器未正常运行 | 手游网游页游攻略大全...
  4. 如何解决老是弹出“com surrogate已停止工作”窗口
  5. Quartz Learn
  6. 问答爆料,Dfinity身份团队AMA 回顾:时间站在我们这边
  7. LSGAN (Least Squares Generative Adversarial Networks)
  8. JS数组对象,过滤掉不要的对象
  9. 龙芯 01 龙芯派1C300B 智龙 V3.42
  10. lvgl移植到linux板子上